AEGIS SGR Installation and Selection


Selecting the Right Size SGR For Your Motor

SGR installation

Installation

For proper operation and optimum performance, install AEGIS SGR™ so that:

  • The conductive MicroFibers. touch the shaft for effective shaft grounding.
     
  • The aluminum brush holder frame extends out from the motor end bell approximately 0.28" (7mm).
     
  • The aluminum brush holder frame has even clearance around the shaft.
  1. Slide SGR over motor shaft and position for even clearance around the shaft.
     
  2. Drill two 1/4" deep holes into motor end bell and tap each with a 6-32 thread or M# thread.
     
  3. Lock SGR in place by fastening brackets to motor end bell using screws provided.

SGR installation